33
6.8 Mode Selection
When wiring is completed the operational mode can be selected.
Mode selection is achieved by means of 3 DIPswitches listed below:
SW1 - Function switch – Fig. 12 Item 7 (see table 6)
SW2 - Address switch – Fig. 12 Item 8 (see table 9)
SW3 - Alarm Delay switch – Fig. 12 Item 9 (see table 10)
Function Switch (SW1):
Modes of operation are selected by DIPswitch (SW1) (Item 7) according to the
selection table in paragraph 4.3.1.
Address Switch (SW2):
The detector has the capability of acting as an addressable device.
The address switch (Item 8) provides 64 addresses, which can be used by the RS-
485 communications link as described in paragraph 4.3.2.
Alarm Delay Switch (SW3):
An Alarm Delay may be required for certain applications. The detector has an
Alarm Delay switch (SW3) (Item 9), permitting time delays from 0 to 3, 5, 10, 15,
20 and 30 seconds respectively (See table 10).
1 Function Switch (SW1): Set all eight (8) switches of SW1 to their appropriate
settings (ON/OFF), to achieve the required functional mode (See paragraph
4.3.1).
2 Address Switch (SW2): Choose the address number from 0 to 63 for the
detector and set switches 1-6 according to the selection table at paragraph
4.3.2
Note: When a multi detector installation is used with RS-485 communication,
then each detector must have an individual address.
3 Alarm Signal Delay Switch (SW3): Set SW3 to the appropriate position to
achieve the required time delay. See paragraph 4.3.3.
4 Verify that the “O” Ring is in its groove in appropriate position on the back
cover.
Close the detector
Connect the housing to the cover using the alignment pin on the back
cover.
Tighten the four (4) socket-head screws to secure the detector housing
to its back cover (tightening torque 1 Kg * M).
5 Install the four (4) set-screws that protect the socket-head screws.
The Detector is now wired, assembled and its operational mode properly set.